- Design
- LCU DX 6.5 kW
- Benefits
- Space-saving solution by installing the internal unit in the VX IT server enclosure or the Micro Data Center
- Maximum energy efficiency due to EC fan technology and IT-based control
- Control of the server inlet temperature
- The inverter-controlled compressor adapts the cooling output to the current heat loss inside the enclosure
- Absorbed thermal energy is emitted directly to the ambient air at the (inverter-controlled) external unit's location, without heating up the installation room
- Applications
- Cooling unit for VX IT server racks and for Micro Data Centers
- Function principle
- The device supports front-to-back air routing typical of IT applications, and regulates the server inlet temperature to the set value
- Material
- Sheet steel, spray-finished
- Colour
- Internal unit: RAL 7035
- External unit: white
- Installation in TS IT
- 482.6 mm (19") levels must be designed as mounting angles and offset in the width by 50 mm off-centre
- The front distance between the 482.6 mm (19") mounting angles and the front edge of the TS frame must be at least 100 mm
- Not suitable for combination with 482.6 mm (19") mounting frame
- Two punched sections with mounting flanges are required for attachment on the inner mounting level
- To separate the hot/cold zones within an enclosure, an air baffle plate for TS IT is required
- A base/plinth is required to route the cable downwards
- Supply includes
- Internal unit (evaporator coil)
- External unit (inverter-controlled)
- 482.6 mm (19") mounting trim panel with display and control components
- Condensate hose
- Note
- Below the operating limit, fluctuations in the air inlet temperature are possible
- The electrical connection is made on the external unit. The internal unit is supplied by the external unit.
- Variant
- Rack cooling
- Useful cooling output L22 L35
- 6.5 kW
- Modulation range
- Device modulates without interruption in the cooling output range between: 3 kW - 6,5 kW
- Total cooling output/Number of fan modules
-
- Total cooling output
- 6.5 kW
- Rated operating voltage
- 230 V, 1~, 50 Hz
- To fit
- with width: = 800 mm
- with height: ≥ 1,800 mm
- with depth: ≥ 1,000 mm
- Temperature range
- Note: The specified operating temperature refers to the external unit
- Refrigerant/cooling medium
- Refrigerant: R410a
- Type of electrical connection
- Connection clamp
- Duty cycle
- 100 %
- Rated current max.
- At 230 V/50 Hz: 15.9 A
- eCl@ss 8.0/8.1
- 27180704
- Packs of
- 1 pc(s)
- Weight/pack
- 121.5 kg
- EAN
- 4028177709300
- Customs tariff number
- 84158200
- –
- ETIM 7.0
- EC000855
- ETIM 6.0
- EC000855
- eCl@ss 8.0/8.1
- 27180704
- eCl@ss 6.0/6.1
- 27180704
- Product description
- SK LCU DX split cooling unit 6,5 kW, Refrigerant-based cooling of TS IT racks, and Micro Data Center, 1 x external unit with inverter regulated compressor, 1 x internal unit, single