- Benefits
- Maximum energy efficiency due to EC fan technology and IT-based control
- Minimal pressure loss at the air end, which in turn minimises the power consumption of the fans
- Optimum adaptability due to dynamic, continuous control of the cold water volume flow
- By using high water inlet temperatures, the proportion of indirect free cooling is increased, which in turn reduces operating costs
- Targeted cooling output due to modular fan units
- Fan modules configurable as n+1 redundancy
- Standard 3-phase connection for electrical redundancy
- With redundant temperature sensor integrated at the air end as standard
- The separation of cooling and enclosure prevents the ingress of water into the server enclosure
- A footprint of max. 0.36 m² for all cooling services
- Improved heat recovery, thanks to high water return temperatures when using LCP CW glycol variants, for example in combination with a heat pump
- Optimum access for maintenance and servicing from the front and rear
- Tool-free replacement of the fan modules
- Function principle
- The hot air is drawn in from the room or hot aisle at the rear of the device and expelled at the front into the cold aisle after cooling. With this product, a raised floor is not necessary.
- IT monitoring
- Monitoring of all system-relevant parameters such as server air intake temperature, server waste air temperature, water inlet/return temperature, water flow, cooling output, fan speed, leakage
- Direct connection of the unit via SNMP over Ethernet
- Integration into RiZone
- Material
- Sheet steel, spray-finished
- Colour
- RAL 7035
- Protection category IP to IEC 60 529
- IP 20
- Options
- Direct connection of additional CMC III sensors is supported
- Racks 2200 mm high
- Variant
- Suite cooling
- Total cooling output/Number of fan modules
- 10 kW / 1
- 20 kW / 2
- 30 kW / 3
- Number of fan modules in supplied state
- 1
- Total cooling output
- 30 kW
- Air throughput (unimpeded air flow)
- At 50 Hz: 4,800 m³/h
- Rated operating voltage
- 230 V, 1~, 50 Hz/60 Hz
- 400 V, 3~, 50 Hz/60 Hz
- Dimensions
- Width: 300 mm
- Height: 2,000 mm
- Depth: 1,200 mm
- Temperature control
- Linear fan control
- Two-way control valve
- Installation in bayed enclosure suite
- Set forward
- Temperature range
- Water inlet: +15 °C
- Refrigerant/cooling medium
- Cooling medium: Water
- Note: Water quality according to unit specifications.
- Type of electrical connection
- Connector
- Duty cycle
- 100 %
- Permissible operating pressure (p. max.)
- 10
- EC fan
- yes
- Fans may be exchanged with the system operational
- yes
- Water connections
- DN 40 (G 1½" external thread)
- eCl@ss 8.0/8.1
- 27180712
- Packs of
- 1 pc(s)
- Weight/pack
- 260 kg
- EAN
- 4028177811652
- Customs tariff number
- 84158300
- ETIM 7.0
- EC002515
- ETIM 6.0
- EC002515
- eCl@ss 8.0/8.1
- 27180712
- eCl@ss 6.0/6.1
- 27180712
- Product description
- SK LCP Inline Protruding R15 CW, 30 kW, RAL 7035, WHD: 300x2000x1200 mm