- Benefits
- Mounted on the rear of the server rack so that the thermal load of the server rack does not have to be dissipated by the ventilation system
- The heat pipe ensures even heat distribution in the heat exchanger, so that the heat exchanger always has a balanced heat load
- A door opening angle of 135° allows rear access to the server enclosure and makes assembly and configuration inside an enclosure easier
- Optimum energy efficiency, as there is no electrical power consumption whatsoever
- Applications
- Air/water heat exchanger for retrofitting to TS IT racks while operational
- Function principle
- The stand-alone unit replaces the rear door
- The waste air is cooled down to room temperature. The heat energy absorbed by the water is transported to the external cold water supply, where it is cooled back down to the required inlet temperature.
- The heat exchanger uses the airflow from the IT equipment and does not require any additional fans for cooling
- Minimal upstream and downstream pressure losses, despite the very compact design
- Water connection from below only
- Colour
- RAL 7035
- Note
- The air throughput (heated waste air) from the active 482.6 mm (19") components installed in the enclosure must be sufficient to overcome the pressure loss from the perforated heat exchanger rear door
- The total cooling output refers to an outlet temperature of 24 °C
- Variant
- Rack cooling
- Total cooling output to DIN EN 14511
- 10 kW
- Total cooling output/Number of fan modules
- 10 kW
-
-
- Total cooling output
- 10 kW
- Dimensions
- Width: 600 mm
- Height: 2,200 mm
- Depth: 105 mm
- Usable height
- 47 U
- Temperature range
- Water inlet: +15 °C
- Refrigerant/cooling medium
- Refrigerant: R134a
- Cooling medium: Water (see Internet for specifications)
- Quantity: 0.65 kg
- Rated volumetric flow
- Air volume: 2,700 m³/h
- Permissible operating pressure (p. max.)
- 6
- Water connections
- DN 25 (G 1" external thread)
- eCl@ss 8.0/8.1
- 27180712
- Packs of
- 1 pc(s)
- Weight/pack
- 78 kg
- EAN
- 4028177717022
- Customs tariff number
- 94032080
- ETIM 7.0
- EC002515
- ETIM 6.0
- EC002515
- eCl@ss 8.0/8.1
- 27180712
- eCl@ss 6.0/6.1
- 27180712
- Product description
- SK LCP Hybrid CW, WHD: 600x2200x105 mm, 10 kW